Product characteristics |
Output signal |
switching signal |
Measuring range |
0…250 bar |
0…3620 psi |
0…25 MPa |
|
Process connection |
threaded connection G 1/4 internal thread |
Application |
Special feature |
Gold-plated contacts |
Media |
liquids and gases |
Conditionally suitable for |
For gaseous media the application is limited to max. 25 bar. |
Medium temperature [°C] |
-25…80 |
Pressure rating |
|
Min. bursting pressure |
|
Type of pressure |
relative pressure |
Electrical data |
Operating voltage tolerance [%] |
20 |
Operating voltage [V] |
24 AC / 18…55 DC |
Current consumption [mA] |
< 50 |
Min. insulation resistance [MΩ] |
100; (500 V DC) |
Protection class |
III |
Reverse polarity protection |
yes |
Overvoltage protection |
yes; (< 60 V DC / < 40 V AC) |
Power-on delay time [s] |
0.5 |
Integrated watchdog |
yes |
Inputs / outputs |
Number of inputs and outputs |
Number of digital outputs: 2 |
Outputs |
Total number of outputs |
2 |
Output signal |
switching signal |
Electrical design |
PNP |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
3 |
Max. voltage drop switching output AC [V] |
3 |
Permanent current rating of switching output AC [mA] |
100 |
Permanent current rating of switching output DC [mA] |
100 |
Switching frequency AC [Hz] |
< 170 |
Switching frequency DC [Hz] |
< 170 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Measuring/setting range |
Measuring range |
0…250 bar |
0…3620 psi |
0…25 MPa |
|
Set point SP |
2…250 bar |
40…3620 psi |
0.2…25 MPa |
|
Reset point rP |
1…249 bar |
20…3600 psi |
0.1…24.9 MPa |
|
In steps of |
|
Accuracy / deviations |
Switch point accuracy [% of the span] |
< ± 0,5 |
Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span] |
< ± 0,25 (BFSL) / < ± 0,5 (LS) |
Hysteresis deviation [% of the span] |
< ± 0,25 |
Long-term stability [% of the span] |
< ± 0,05; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] |
0,2; (-20…80 °C) |
Temperature coefficient span [% of the span / 10 K] |
0,2; (-20…80 °C) |
Response times |
Delay time programmable dS, dr [s] |
0; 0,2…50 |
Operating conditions |
Ambient temperature [°C] |
-20…80 |
Storage temperature [°C] |
-40…100 |
Protection |
IP 67 |
Tests / approvals |
EMC |
EN 61000-4-2 ESD |
4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated |
10 V/m |
EN 61000-4-4 Burst |
2 kV |
EN 61000-4-5 Surge |
0,5/1 kV |
EN 61000-4-6 HF conducted |
10 V |
|
Shock resistance |
DIN IEC 68-2-27 |
50 g (11 ms) |
|
Vibration resistance |
DIN IEC 68-2-6 |
20 g (10…2000 Hz) |
|
MTTF [years] |
199 |
Pressure Equipment Directive |
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data |
Weight [g] |
261 |
Materials |
stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; EPDM/X |
Materials (wetted parts) |
stainless steel (1.4305 / 303); ceramics; FKM |
Min. pressure cycles |
100 million |
Process connection |
threaded connection G 1/4 internal thread |
Restrictor element integrated |
no (can be retrofitted) |
Displays / operating elements |
Display |
Display unit |
3 x LED, green |
switching status |
2 x LED, yellow |
function display |
alphanumeric display, 4-digit |
measured values |
alphanumeric display, 4-digit |
|
Remarks |
Remarks |
BFSL = Best Fit Straight Line |
LS = limit value setting |
|
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
Connector: 1 x M12; Contacts: gold-plated |