Product characteristics |
Electrical design |
PNP/NPN; (parameterisable) |
Output function |
normally open / normally closed; (parameterisable) |
Communication interface |
IO-Link |
Housing |
threaded type |
Dimensions [mm] |
M30 x 1.5 / L = 65 |
Electrical data |
Operating voltage [V] |
15…30 DC |
Current consumption [mA] |
< 30 |
Protection class |
II |
Reverse polarity protection |
yes |
Outputs |
Electrical design |
PNP/NPN; (parameterisable) |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
2.5 |
Permanent current rating of switching output DC [mA] |
100 |
Switching frequency DC [Hz] |
300 |
Analogue voltage output [V] |
0…10; (linear; gradient: 1,111 V/mm; for frontal approach and for target made of mild steel: 30 x 30 x 1 mm) |
Min. load resistance [Ω] |
2000 |
Short-circuit protection |
yes |
Overload protection |
yes |
Detection zone |
Measuring range [mm] |
1…10 |
Switch point IO-Link [mm] |
1.88…9.35 |
Accuracy / deviations |
Correction factor |
steel: 1 / stainless steel: 0.8 / brass: 0.5 / aluminium: 0.5 / copper: 0.4 |
Hysteresis [% of Sr] |
3…15 |
Note on hysteresis |
|
Linearity error of analogue output [%] |
± 1; (of the final value of the measuring range) |
Repeatability analogue output [%] |
± 1; (of the final value of the measuring range) |
Temperature coefficient [%/K vom MEW] |
±0,15 |
Temperature drift [% vom MEW] |
±5 |
Response times |
Response time [ms] |
< 10 |
Interfaces |
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 |
Profiles |
Smart Sensor: Identification and diagnosis; Multi-channel, two setpoint switching sensor, type 0 Generic Profiled Sensor; Teach Channel |
SIO mode |
yes |
Required master port type |
A |
Min. process cycle time [ms] |
3.2 |
IO-Link process data (cyclical) |
function |
bit length |
process value |
16 |
device status |
4 |
binary switching information |
2 |
|
IO-Link functions (acyclical) |
switching cycles counter; switch-on cycle counter; operating hours counter; internal temperature; application specific tag |
Supported DeviceIDs |
Type of operation |
DeviceID |
Default |
1206 |
|
Note |
For further information please see the IODD PDF file under “Downloads” |
|
Operating conditions |
Ambient temperature [°C] |
-25…80 |
Protection |
IP 65; IP 66; IP 67; IP 68; IP 69K |
Tests / approvals |
EMC |
EN 61000-4-2 ESD |
4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated |
10 V/m |
EN 61000-4-4 Burst |
2 kV |
EN 61000-4-6 HF conducted |
10 V |
EN 55011 |
class B |
|
Vibration resistance |
EN 60068-2-6 Fc |
20 g (10…3000 Hz) / 50 sweep cycles, 1 octave per minute, in 3 axes |
|
Shock resistance |
EN 60068-2-27 Ea |
100 g 11 ms half-sine; 3 shocks each in every direction of the 3 coordinate axes |
|
Continuous shock resistance |
EN 60068-2-27 |
40 g 6 ms; 4000 shocks each in every direction of the 3 coordinate axes |
|
Fast temperature change |
EN 60068-2-14 Na |
TA = -25°C; TB = 80°C; t1 = 30 min; t2 = < 10 s 50 cycles |
|
MTTF [years] |
222 |
UL approval |
Ta |
-25…60 °C |
Enclosure type |
Type 1 |
voltage supply |
Limited Voltage/Current |
UL Approval no. |
A024 |
File number UL |
E174191 |
|
Mechanical data |
Weight [g] |
151 |
Housing |
threaded type |
Mounting |
flush mountable |
Dimensions [mm] |
M30 x 1.5 / L = 65 |
Thread designation |
M30 x 1.5 |
Materials |
Housing: brass white bronze coated; sensing face: PBT orange; LED-Fenster: PEI; lock nuts: brass white bronze coated |
Tightening torque [Nm] |
50 |
Displays / operating elements |
Display |
target in measuring range |
4 x LED, yellow lights |
target outside measuring range |
4 x LED, yellow flashing |
|
Accessories |
Items supplied |
|
Remarks |
Pack quantity |
1 pcs. |
Electrical connection – plug |
Connection |
Connector: 1 x M12 |