| SV7200 Product characteristics |
| Number of inputs and outputs |
Number of digital outputs: 2 |
| Measuring range |
|
| Process connection |
threaded connection G 3/4 DN20 |
| Application |
| Special feature |
Gold-plated contacts |
| Application |
for industrial applications |
| Media |
water |
| Medium temperature [°C] |
-10…90 |
| Pressure rating [bar] |
12 |
| Pressure rating [Mpa] |
1.2 |
| Note on pressure rating |
|
| MAWP (for applications according to CRN) [bar] |
4.3 |
| Electrical data |
| Operating voltage [V] |
18…30 DC |
| Current consumption [mA] |
< 30 |
| Min. insulation resistance [MΩ] |
100; (500 V DC) |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time [s] |
< 3 |
Inputs / outputs
|
| Number of inputs and outputs |
Number of digital outputs: 2 |
| Outputs |
| Total number of outputs |
2 |
| Output signal |
switching signal; frequency signal; IO-Link; (configurable) |
| Electrical design |
PNP/NPN |
| Number of digital outputs |
2 |
| Output function |
normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] |
2.5 |
| Permanent current rating of switching output DC [mA] |
100 |
| Short-circuit protection |
yes |
| Overload protection |
yes |
| SV7200 Measuring/setting range |
| Measuring range |
|
| Display range |
|
| Resolution |
|
| Set point SP |
|
| Reset point rP |
|
| Frequency end point, FEP |
|
| In steps of |
|
| Frequency at the end point FRP [Hz] |
100…1000 |
| Measuring dynamics |
1:20 |
| SV7200 Temperature monitoring |
| Measuring range [°C] |
-10…90 |
| Display range [°C] |
-30…110 |
| Resolution [°C] |
0.5 |
| Set point SP [°C] |
-9…90 |
| Reset point rP [°C] |
-10…89 |
| In steps of [°C] |
0.5 |
| Frequency start point, FSP [°C] |
-10…70 |
| Frequency end point, FEP [°C] |
10…90 |
| Frequency at the end point FRP [Hz] |
100…1000 |
Accuracy / deviations
|
| Flow monitoring |
| Accuracy (in the measuring range) |
± 2 % MEW |
| Repeatability |
± 0,5 % MEW |
| Temperature monitoring |
| Accuracy [K] |
± 1 |
| Response times |
SV7200 Flow monitoring
|
| Response time [s] |
1; (dAP = 0) |
| Damping process value dAP [s] |
0…5 |
| Temperature monitoring |
| Dynamic response T05 / T09 [s] |
T09 = 6 |
Software / programming
|
| Parameter setting options |
hysteresis / window; normally open / normally closed; switching logic; frequency output; switch-on/switch-off delay; Damping; Display unit |
| SV7200 Interfaces |
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.1 |
| SDCI standard |
IEC 61131-9 |
| Profiles |
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
| SIO mode |
yes |
| Required master port type |
A |
| Process data analogue |
2 |
| Process data binary |
2 |
| Min. process cycle time [ms] |
3 |
| Supported DeviceIDs |
| Type of operation |
DeviceID |
| Default |
492 |
|
Operating conditions
|
| Ambient temperature [°C] |
0…60 |
| Note on ambient temperature |
| medium temperature < 80 °C |
| medium temperature < 90 °C: 0…50 °C |
|
| Storage temperature [°C] |
-20…80 |
| Protection |
IP 65; IP 67 |
| SV7200 Tests / approvals |
| EMC |
| DIN EN 61000-6-2 |
|
| DIN EN 61000-6-3 |
|
|
| CPA approval |
| model number |
001VO |
| accuracy class |
– |
| maximum allowable error |
± 2 % FS |
| Q (min) |
0,36 m³/h |
| Q (t) |
1,2 m³/h |
| Q (max) |
6 m³/h |
|
| Shock resistance |
| DIN EN 60068-2-27 |
5 g (11 ms) |
|
| Vibration resistance |
| DIN EN 60068-2-6 |
with water / 10…50 Hz 1 mm |
|
with water / 50…2000 Hz 2 g |
|
| MTTF [years] |
342 |
| UL approval |
|
| Pressure Equipment Directive |
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| SV7200 Mechanical data |
| Weight [g] |
484.5 |
| Materials |
stainless steel (1.4404 / 316L); PC; PBT+PC-GF30; PPS; TPE-U |
| Materials (wetted parts) |
stainless steel (1.4404 / 316L); ETFE; PA 6T; PPS; FKM |
| Tightening torque [Nm] |
30 |
| Process connection |
threaded connection G 3/4 DN20 |
| Remarks |
| Remarks |
| MW = measured value |
| MEW = Final value of the measuring range |
|
| Pack quantity |
1 pcs. |
| Electrical connection |
| Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |
| Diagrams and graphs |
| Pressure loss |
| dP |
Pressure loss |
| Q |
volumetric flow quantity |
|
| pressure rating (bar) |
|