V9060iT HMI Hakko Fuji Electric Monitouch

Jual HMI Hakko V9060iT Fuji Electric Monitouch

HMI Hakko V9060iT

Jual HMI Hakko V9060iT Fuji Electric Monitouch }

V9 Advanced Lineup

V9101iW series

V9071iW series

V9 Standard Lineup

V9150iX series

V9120iS series

V9100iS series

V9080iS series

 

V9 Lite Lineup

V9100iC series

V9080iC series

V9060iT series

 

HMI Hakko V9060iT Dimensions and Part Names

V9060iT
V9060iT
Power supply
Rated voltage DC24V
Permissible range of voltage ±10%
Permissible momentary power failure within 1ms
Demand (maximum rating) 13W or less
Insulation resistance DC500V 10MΩ or more
V9060iT
Physical environment
Ambient temperature 0~50℃*1
Ambient humidity 85%RH or less (without dew condensation)*1
Operation altitude 2,000 meters or lower
Atmosphere Not to be exposed to corrosive gas, or conductive dust
Storage temperature -10~60℃*1
Storage temperature 85%RH or less (without dew condensation)*1
Overvoltage category Category II
Pollution degree Pollution degree 2
V9060iT
Mechanical operating conditions
Resistance to oscillation Complies with JIS B 3502 (IEC61131-2) Vibration frequency: 5~9Hz, pulsating with:3.5mm,
9~150Hz, Acceleration: 9.8m/s2(1G),X,Y,Z: 3 directions (10 times each)
Resistance to shock Complies with JIS B 3502 (IEC61131-2) Peak acceleration: 147m/s2(15G), X,Y,Z:
3 directions, three times each (18 times in total)
Electric operating conditions Resistance to noise Noise voltage: 1,000Vp-p, pulse width: 1μs, pulse rise time: 1ns
Resistance to static discharge Complies with IEC61000-4-2, contact: 6kV, air: 8kV
V9060iT
Installation conditions
Grounding Grounding resistance: Less than 100Ω, FG/SG separation
Structure Protection structure: Front case: IP66, Type 4X/13(when water-proof gasket is used), Rear case: IP20, single unit, installation method: panel mounting
Cooling system Natural air cooling
Dimensions W*H*D(mm) 182.5×138.8×53.0
Dimensions W*H*D(mm) 174.0×131.0(+0.5/-0)
Case color Light gray
(black front housing for black model)
Material PC resin
  • *1: Use at a wet-bulb temperature of 39°C or less because higher temperatures may cause failure.

HMI Hakko V9060iT Performance Specifications

Screen memory (FROM) 64MB
Backup memory (SRAM) 800KB
V9060iT
Display
Display device TFT color LCD
Resolution 640×480
Display size 5.7″
Colors 260 thousand *2
Backlight LED
Backlight life 50,000 hours
Touch switch Type Analog resistance film
Function switch Quantity 6
V9060iT
External interface
D-Sub 9-pin (CN1)*3 RS-232C, RS-485(two-wire system), RS-422(four-wire system), Asynchronous type,
Data length: 7,8 bits, Parity: even, odd, none,
Stop bit: 1, 2 bits, Baud rate: 4800, 9600, 19200, 38400, 57600, 76800, 115200 bps
Modular 8-pin
(MJ1/ MJ2)
RS-232C, RS-485(two-wire system), RS-422(four-wire system)*4 , Asynchronous type,
Data length: 7,8 bits, Parity: even, odd, none, Stop bit: 1, 2 bits, Baud rate: 4800, 9600,
19200, 38400, 57600, 76800, 115200, 187500*5 bps
SD card One card slot provided as standard
Ethernet 1ch,
Baud rate: 100Mbps, 10Mbps
Wireless LAN
USB Type A、Type mini-B(Ver.2.0)
Sound output
V9060iT
Clock
Backup period 5 years (Ambient temperature 25°C)
Calendar accuracy Gap ±90 sec. per month (Ambient temperature 25°C, when power is not supplied)
V9060iT
Standard
CE marking EN61000-6-2, EN61000-6-4, EN50581
UL・cUL UL61010-1、UL61010-2-201*6 、ANSI/ISA 12.12.01
KC *7 Compliant
Radio Act
V9060iT
Classification Standard
Nippon Kaiji Kyokai (NK)
American Bureau of Shipping (ABS)
Lloyd’s Register of Shipping (LR)
Det Norske Veritas (DNV)
  • *2: For displaying pictures, 3D parts,video, and RGB input (excluding high-speed mode) only. Other parts are displayed in 65,536 colors.
  • *3: Optional unit (DUR-00) is required for the V9071iW and V9060iTD.
  • *4: 187,500 bps (four-wire system) for the V9071iW and V9060iTD MJ2 only.
  • *5: Only for Siemens MPI (Incompatible with DUR-00).
  • *6: Only for Hardware Ver. f or later. Applicable standard for Hardware Ver. a to e is UL 508.
  • *7: Black model not certified